• ademco vista 250 manual

    ademco vista 250 manual

    Download Link: ➡ ademco vista 250 manual



    File Name: ademco vista 250 manual.pdf
    Size: 4233 KB
    Type: PDF, ePub, eBook
    Category: Book
    Uploaded: 3 May 2019, 13:42 PM
    Rating: 4.6/5 from 717 votes.


    Last checked: 1 Minutes ago!









    ⬆ LINK ⬆




















    In order to read or download ademco vista 250 manual ebook, you need to create a FREE account.

    eBook includes PDF, ePub and Kindle version



    ✔ Register a free 1 month Trial Account.
    ✔ Download as many books as you like (Personal use)
    ✔ Cancel the membership at any time if not satisfied.
    ✔ Join Over 80000 Happy Readers


    Book Descriptions:

    ademco vista 250 manual

    A keypad software version of 3-2-07 or later is required for use with the Vista Turbo Series. Software updates can be installed easily using the removable SD card supplied with the keypad. This note affects graphical keypads only.The following table lists the differences between the VISTA-128BPT and the VISTA-250BPT control panels. All other features are identical. Feature Number of Zones Number of User Codes Number of Access Cards Event Log Capacity VistaKey Modules VISTA-128BPT 128 150 250 512 8 VISTA-250BPT 250 250 500 1000 15 Triggers the built-in sounders on other hardwired smoke detectors if one smoke detector annunciates an alarm. This feature requires a 4204 Relay Module. Provides tamper supervision on the hardwire zones. Supports up to 241 additional expansion zones (119 for the VISTA-128BPT) using a built-in polling (multiplex) loop.All other RF receivers and transmitters are not listed for UL Commercial Burglary applications. Wireless devices are not ULC Listed and cannot be used for ULC Installations. Remote Interactive Service (RIS) allows access from a wireless phone or web browser via any TC2 compatible The trouble report code is used to report the masking. Battery sensing hardware that can sense when the battery voltage is too low and prevents deep discharging from not occurring. Supports up to 31 addressable devices, (keypads, RF receivers, relay modules, etc.). Supervises devices (keypads, RF receivers, and relay modules) and individual relays (up to 32), as well as system zones (RF receivers and keypad panics). Supports the ADEMCO 4286 VIP Module, which allows access to the system from either a remote location or on the premises Can arm the system with zones faulted (Vent Zone). These zones are automatically bypassed and can be programmed to automatically unbypass when the zone restores. These zones must be restored before the exit delay expires, otherwise an alarm is generated.

    • honeywell vista 250 manual, ademco vista 250 programming manual, ademco vista 250 user manual, honeywell vista 250 installation manual, honeywell vista 250 user manual, ademco vista 250 manual, honeywell vista 250 manual, ademco vista 250 programming manual, ademco vista 250 user manual, honeywell vista 250 installation manual, honeywell vista 250 user manual, ademco vista 250 manual.

    Product availability, at the moment, is in flux. If you order today, depending on the product, there may be a significant delay in shipping it to you. We apologize for any delays, and assure you that products will be shipped as soon as we can get them. Before COVID, we had significant stock of nearly every popular product that we sell. But demand has outpaced our supplier's ability to meet it, and has exhausted the stock we had purchased to meet increased demand during the government-mandated lockdowns. If you need the product right away, it is unlikely we will be able to accommodate you. For that we apologize. We ask for your patience as we all navigate this unique situation together. Be nice to our employees, they are doing their best to answer your questions and get your product to you as quickly as they can.If you are here to get product quickly because you are unable to get the product at your usual supplier, rest assured, we are also out of the product and won't be able to fulfill your order in a timely manner. Like our end-users, we will be delivering products as soon as we get them in. For the purpose of improving our site, we’d like to know if you are one of the following: How do I go about resetting the installer code? A-1 UL365 Police Station Connected Burglar Alarm. A-2 California State Fire Marshal (CSFM) and UL Residential Fire Battery Backup Requirements. A-2 ULC Installation Requirements. A-2 B-1 APPENDIX C: Specifications. C-1 APPENDIX D: Contact ID Codes.Please read each warning carefully. This symbol also denotes warnings about physical harm to the user. These prompts are shown in a single-line box. The differences between the two panels are outlined in the SIA CP-01 Quick Reference Chart located at the beginning of this manual. The Vista Turbo Series is compatible with up to six (6) 6272 graphical keypads as well as later model graphical keypads. These keypads may require a software update in order to be fully compatible.

    The feature is enabled by Zone in Zone Programming. The LED will remain enabled until the Burglary Walk Test mode is exited. NOTE: Regardless of Smart Mode, Tamper and Supervision Failure are sent without delay. Some motion detectors, including the DT7500SN, have an “Anti-Mask” feature that will alert the panel when the lens has been blocked. For DIP switch settings related to this feature, refer to the motion detector documentation. 5800 wireless and V-Plex smoke detectors can send a report to the panel when they determine that their sensitivity has deteriorated beyond the sensor’s ability to compensate internally (Dirty). When programmed as a “Smart Contact” in zone programming, a sensor which shows a high or low sensitivity condition will trigger a message on the keypad, a dialer report, and an event log entry. The display message will indicate HSENSxxx or LSENSxxx, where xxx is the zone number. Provides up to 60 installer-defined, custom words that can be used for zone descriptors. Provides 32 keypad macro commands (each macro is a series of keypad commands of up to 32 keystrokes) using the A, B, C, and D keys by partition. Provides cross-zone capability, which helps prevent false alarms by preventing a zone from going into alarm unless its cross-zone is also faulted within a 5-minute period. Contains a built-in User Manual, which provides the end user with a brief explanation of the function of a key when the user presses any of the function keys on the keypad for 5 seconds. Provides an RS232 input (TB4) for serial data. This is useful for interfacing the system with Automation software. Automation software cannot be used if a serial printer is used on the system.These areas are called partitions. A Partitioned system allows the user to disarm certain areas while leaving other areas armed, or to limit access to certain areas to specific individuals.

    Can Quick Exit an armed premises without having to disarm and then rearm the system. Can automatically bypass specific zones if no one exits the premises after arming (Auto-STAY). Auto-STAY will not occur if the system is armed via an RF transmitter, VIP module, scheduling, access control, keyswitch, RS232 (TB4) automation or downloading. Can bypass a group of zones with one set of keystrokes. Can control eight separate areas independently, each functioning as if it had its own separate control. Provides a Common Lobby partition, which can be programmed to arm automatically when the last partition is armed, and to disarm when the first partition is disarmed. Provides a Master partition (9), used for the purpose of viewing the status of all partitions at the same time. Can display fire, burglary, panic, and trouble conditions at all other partitions’ keypads (selectable option). Provides an End User Output Programming Mode, allowing the user to control outputs. Supports up to 15 VistaKey modules (15 access points) (VISTA-128BPT supports 8 modules), which are used for access control. It is a single-door access control module. Support up to 500 access cards (250 in VISTA-128BPT). Can store access control events in the event log. The system is shipped defaulted for Contact ID communication. It is the only format capable of uniquely reporting all 250 zones, as well as openings and closings for all 250 users. If you need to update your MX8000 receiver, contact your distributor. A Dialer Queue Overflow report (E354) will be sent if the report queue goes beyond its limits. Life Safety events may go beyond 37 (up to 128) if there are no Burg events in the queue. Provides an event log (history log) that can store up to 1000 events (512 for VISTA-128BPT). The panel will indicate “PHONE LINE CUT” on the keypad when phone line voltage drops below 2VDC for approximately 120 seconds.This prevents the polling loop from slowing down due to high bus activity in busy areas.

    Steady burglar alarm sounds. In order to affect that partition, the user must use a code that has access to that partition. Also, in order for a user of any partition to log on to Partition 9 to view the status of all partitions, that user must have access to all partitions. Otherwise, access is denied. A Master keypad uses the same panics as Partition 1. Master keypad panics are sent to Partition 1, and will activate on Partition 1. Therefore, panics must be programmed for Partition 1. NOTE: All references in this manual for number of zones, number of user codes, number of access cards, and the event log capacity, use the VISTA-250BPT’s features. See SECTION 1: General Description for the table listing the differences between the VISTA-128BPT and the VISTA-250BPT control panels. The back of the cabinet has 4 holes for this purpose. To provide certificated burglary service for UL installations, refer to the special requirements and Figure 3-2 Cabinet Attack Resistance Considerations to follow. For UL Commercial Burglary installations that require ATTACK RESISTANCE, use the cabinet included in the COM-UL Commercial Enclosure. Insert the key into the lock. Position the lock in the hole, making certain that the latch will make contact with the latch bracket when the door is closed. When correctly positioned, insert supplied lock clip on the inside of the cabinet into the slots on the lock cylinder.Mount the clip-on tamper switch (supplied) to the cabinet's right side wall as shown in the diagram below, and wire it to one of the hardwire zones. Use a bell with a tamper-protected housing such as the ADEMCO AB12M. The bell housing's tamper switch and inner tamper linings must also be wired to the hardwire zone. Assign the tampers’ hardwire zone to a burglary partition. Program it for 24-hr.Remaining wires do not need to be run in conduit. All wiring that is not run in conduit must exit from the knockout openings on the bottom or back of the cabinet.

    Each system user can be assigned to operate any or all partitions, and can be given a different authority level in each. Before anything can be assigned to those partitions, you must first determine how many partitions (1-8) are required. Following are some facts you need to know about partitioning. The zones assigned to a partition will be displayed on that partition's keypad(s). It can also be assigned to Partition 9 if Master keypad operation is desired. (See “Master Keypad Setup and Operation” later in this section.) Assign users to partitions. Program partition-specific fields (see the Data Field Descriptions section). An example of this might be in a medical building where there are two doctors’ offices and a common entrance area (see example that follows explanation). The Common Lobby feature employs logic for automatic arming and disarming of the common lobby. Two programming fields determine the way the common lobby will react relative to the status of other partitions.Therefore, you would want to program a partition to affect and arm the lobby if the users of that partition are expected to be the last to leave the building. The lobby must be armed separately, after arming all affecting partitions first. This causes the lobby to arm last. A Master keypad reflects the status of the entire system (Partitions 1-8) on its display at one time. This is useful because it eliminates the need for a building security officer to have to log on to various partitions from one partition's keypad to find out where an alarm has occurred. The Armed LED on a Master keypad is lit only if all partitions have been armed successfully. Otherwise, if no keys are pressed for 2 minutes, the system automatically returns to the master partition The sounder on a Master keypad reflects the sound of the most critical condition on all of the partitions. The priority of the sounds, from most to least critical, is as follows: 1. Pulsing fire alarm sounds 2. T4 CO alarm sounds 3.

    If the communicator is connected to a PABX, be sure it has a backup power supply that can support the PABX for 24 hours (central station) or 60 hours (remote station). Many PABXs are not power-backed up, and this can result in a communication failure if power is lost.The 2K EOL resistor must be connected across the loop wires at the last device.The alarm current on zone 1 supports only one smoke detector in the alarmed state. Compatible 2-Wire Smoke DetectorsTo wire 2-wire smoke detectors to zone 1, perform the following steps: Step 1 2 3 Action Select up to 16 2-wire smoke detectors from the list of compatible detectors. Connect 2-wire smoke detectors across zone 1 terminals (10 and 11) as shown in Figure 3-10. Observe proper polarity when connecting the detectors. Connect the EOL resistor at the last detector in the loop across the zone 1 terminals. The EOL resistor must be connected across the loop wires at the last detector. Some compatible 4-wire smoke detectors are listed below.Action Select 4-wire smoke detectors (see list of compatible detectors shown previously). Connect detectors (including heat detectors, if used) across terminals of the zone selected. All detectors must be wired in parallel. See Figure 3-11. NOTE: If you are using the J7 output trigger to reset the smoke detectors, refer to Smoke Detector Reset later in this section for the wiring instructions. Connect the EOLR at the last detector in the loop across the zone’s terminals. You must connect the EOLR across the loop wires at the last detector. For the normally open sensor, program the zone for trouble on open. To wire a tamper switch on a hardwired zone, connect the EOL resistor at the last detector in the loop across the zone’s terminals. You must connect the EOL resistor at the last detector for proper operation of the tamper supervision. NOTE: These zones cannot be programmed for any 24 hour zone type and that tamper supervision is only in the disarmed state. When armed goes into alarm.

    NOTE: For zones with a response type of 9 or 16 (Fire), the tamper selection must be “0” none.The maximum current draw of all devices on the polling loop cannot total more than 128mA (unless the system uses a 4297 Polling Loop Extender Module). Devices that can be programmed via either DIP switches or the built-in unique serial number must be set for the serial number mode operation. You can wire from device to device, or have multiple branches connected directly to the control panel in a star configuration. Compatible Polling Loop DevicesAlways locate polling loop wiring at least 6 inches (15cm) of AC power, telephone, or intercom wiring. The polling loop carries data between the control panel and the devices; interference on this loop can cause an interruption of communication. The polling loop can also cause outgoing interference on the intercom or phone lines. If this spacing cannot be achieved, shielded wire must be used. (Note that the maximum total wire length supported is cut in half when shielded wire is used.) Set the DIP switches in the device (if required). Refer to the device’s instructions. Mount each device in the desired location. Run wires from the control panel to each device on the polling loop (see Figure 3-14). Wire each device to the polling loop, making sure of the correct polarity (refer to the device’s instructions). NOTE: If you are using serial number devices, and intend to enroll each device through the keypad automatically, wire no more than 25 of these devices to the control at a time. Then power up and program them before connecting the next 25. Leave previously enrolled devices connected. If you intend to manually enter the serial numbers via the keypad or the Compass downloading software, all the devices may be connected before powering up to program. If the panel is armed when a device fails, and the zone is a burglary zone, the system will go into alarm.

    All unused knockouts must be plugged using the disc plugs and carriage bolts (supplied), as indicated in the diagram below. Fasten the cabinet door to the cabinet backbox using the 18 one-inch-long Phillips-head screws (supplied) after all wiring, programming, and checkout procedures have been completed.Mount a shock sensor such as the ASC-SS1 to the control's backbox. Follow the manufacturer's instructions for proper sensor mounting. This sensor also must be wired to a hardwire zone. For safe and vault applications, a UL Listed contact must be used inside the cabinet through one of the knockouts for pry-off tamper purposes. This sensor also must be wired to a hardwire zone. Refer to Figure 3-3 (Detail B). Make sure the clip orientation is exactly as shown in the diagram to avoid damage. This will also avoid problems with insertion and removal of the PC board. Insert the top of the circuit board into the slots at the top of the cabinet. Make certain that the board rests in the slots as indicated (Detail A). Swing the base of the board into the mounting clips and secure the board to the cabinet with the accompanying screws. Dress field wiring away from the microprocessor (center) section of the PC board. Use the loops on the left and right sidewalls of the cabinet for anchoring field wiring using tie wraps (Detail C). These steps are important to minimize the risk of panel RF interference with television reception. The maximum wire run length from the control to a keypad, which is homerun back to the control must not exceed the lengths listed in the table. Run field wiring from the control to the keypads (using standard 4-conductor cable of the wire gauge determined in step 1).Set an alpha keypad for address 00 and other keypads for higher addresses (00 and 01 are enabled in the system's default program). Any keypads set for address 02 and above will appear blank until they are enabled in the system's program. Check your wiring.

    Supplementary Power Supply for Additional Keypads When the control’s auxiliary power load for all devices exceeds 750mA, you can power additional keypads from a regulated 12VDC power supply (e.g., ADEMCO AD12612 (1.2A)). Use a UL Listed, battery-backed supply for UL installations. Connect the additional keypads as shown in Figure 3-5, using the keypad wire colors shown.UL1023 Household Burglary Installations For Household Burglary installations, the total current drawn from the alarm output must not exceed 1.7A. A battery must be installed, as the battery supplies current from the combined auxiliary power, polling loop, and alarm output in excess of 750mA. Non-UL Installations For non-UL installations, the total current drawn from this output can be up to 1.7A. A battery must be installed, as the battery supplies current in excess of 750mA. Up to two 719 sirens can be used wired in parallel. The zone displays on the keypads, reports to the event log, and transmits to the central station (if programmed) on Partition 1. The Contact ID event code is 321, Bell Trouble. Wiring the Alarm Output The wiring of the alarm output depends upon whether you are going to supervise the output or not. Use the appropriate procedure below for your application. Wire the siren driver to the control and to the speaker(s). (See the driver’s instructions.) Cut the blue jumper on the upper left-hand corner of the panel’s PC board. Program Zone 970 with no response type (00). Cut the blue jumper on the upper left-hand corner of the panel’s PC board. Program Zone 970 with no response type (00). It is the only format capable of uniquely reporting all 250 zones, as well as openings and closings for all 250 users. This requires central stations to be equipped with the Honeywell MX8000 receiver or equivalent. If you need an update, contact your distributor. To prevent the risk of shock, disconnect phone lines at the telco jack before servicing.

    A trouble on zone 997 prevents a partition from being armed, unless all polling loop zones on that partition are bypassed. Refer to Figures 3-15 and 3-16, to follow.All other RF receivers and transmitters are not listed for UL Commercial Burglary applications. Wireless devices are not ULC Listed and cannot be used for ULC Installations. The control checks for this condition every 45 seconds. You may only mount the 5881ENHC its own plastic housing. Otherwise, the receiver constantly reports a tamper condition. The control checks the receiver connections about every 45 seconds. Use two identical receivers to provide either a greater area of coverage or redundant protection. They must be set for different addresses. NOTE: No more than two receivers can be installed. Any zone from 1 to 250 can be used as a 5800 Series wireless zone, with the exception of zone 64 (reserved for a wireless keypad). Do not place it on or near metal objects. Install the RF receiver at least 10 feet from the control panel or any keypads, to avoid interference from the microprocessors in these units. If dual receivers are used: a. They must be at least 10 feet from each other, as well as from the control panel and remote keypads. b. Each receiver must be set to a different device address. The receiver set to the lower address is considered the st 1 RF receiver for supervisory purposes. c. The House IDs must be the same. d. Using two receivers does not increase the number of transmitters the system can support (249 zones using the 5881ENHC, plus a wireless keypad). Set the DIP switches in the receiver for the address (01-07). See Figure 3-18. Make sure the address setting is not being used by another device (keypad, relay module, etc.). If installing a 5881ENHC, install a flat-head screw (supplied) in the case tamper tab as shown in Figure 3-17. When the receiver is pried from the wall, the tamper tab will break off and remain on the wall.

    This will activate a tamper switch in the receiver and cause generation of a tamper signal. Note that this signal will also be generated when the receiver’s front cover is removed. Connect the receiver’s wire harness to the keypad terminals (6, 7, 8, and 9). Plug the connector at the other end of the harness into the receiver. Refer to the Installation Instructions provided with the receiver for installations regarding antenna mounting, etc. OBSERVE 20 ft. MAX. To install the 5800TM, perform the following steps: Step 1 Action Mount the unit using its accompanying mounting bracket near the RF receiver. The 5800TM must not be installed within the control cabinet. It must be between one and two feet from the receiver’s antennas. Set the module for the appropriate address. For Address Setting 28 cut the red jumper; for Address 29 cut the white jumper; for Address 30 cut both jumpers. Make sure the address setting is not being used by another device (keypad, relay module, etc.). Connect the module’s wire harness to the keypad terminals (6, 7, 8, and 9). Plug the connector at the other end of the harness into the module. The receiver now “sniffs” for any House IDs in the area and displays them. Keep the receiver in this mode for 2 hours. Use a House ID that is not displayed. Transmitter Input Types All transmitters have one or more unique factory-assigned input (loop) codes. Transmitters can be programmed as one of the following types:The control panel automatically restores the zone to “ready” after a few seconds. This type is designed for facilities with multiple motion detectors that may fault and restore simultaneously. The transmitter must remain within the receiver’s range. Sends periodic check-in signals, as well as fault, restore, and low-battery signals. Sends all the signals that the RF type does, but the control does not supervise the check-in signals. The transmitter may therefore be carried off-premises. These send only fault signals.

    They do not send low-battery signals until they are activated. The transmitter may be carried off-premises. If at least one check-in is not received from each supervised transmitter within a programmed period (field 1?31), the “missing” transmitter number(s) and “CHECK” or “TRBL” are displayed. Unsupervised RF transmitters (5802MN, 5804) may be carried off the premises. Some transmitters have built-in tamper protection, and annunciate a “CHECK” or “TRBL” condition if covers are removed. If a loss of supervision occurs on a transmitter programmed for Fire, it reports in Contact ID as a Fire Trouble (373), not Loss of Supervision (381), to the central station. Factors such as humidity, high or low temperatures, as well as large swings in temperature may all reduce the actual battery life in a given installation. The wireless system can identify a true low battery situation, thus allowing the dealer or user of the system time to arrange a change of battery and maintain protection for that point within the system. Button-type transmitters (e.g., 5802, 5804 and 5805-6) should be periodically tested, as these transmitters do not send supervisory check-in signals. Each device must be programmed as to how to act (ACTION), when to activate (START), and when to deactivate (STOP). Installing a 4204 Relay Module To install the relay modules, see Figure 3-19 and perform the following steps: Step 1 2 3 Action Set the 4204 DIP switches for a device address 01-15. Do not use an address being used by another device (keypads, RF receivers, etc.). Mount the 4204 Module per the instructions provided with them. Connect the module’s wire harness to the control (6, 7, 8, and 9). Plug the connector (other end of harness) to the module. If you are mounting remotely, homerun each module to the control. The table below shows the maximum wire run lengths.

    Be sure to observe polarity Installing X10 Devices X-10 devices are either plugged into standard AC outlets or wired into the AC electrical system by a licensed electrician, depending on the type of device used. X-10 devices require the use of a 1361X10 transformer in place of the regular 1361 transformer. X-10 devices respond to “on” and “off” commands sent from the panel through the 1361X10 transformer. To connect the 1361X10 transformer, see Connecting the Transformer, later in this section. A subsequent short across Zone 7 clears the alarm memory indication and resets 2-wire smoke detectors (if used). LED Indications. For UL Commercial Burglary installations, the tamper switch must be wired to a zone (zone 7 in Figure 3-20). When the keyswitch is removed from the wall, the tamper switch opens, causing an alarm or trouble on the zone. This also causes the control to disable keyswitch operation until the tamper is restored and the associated partition is disarmed. Wiring for the Remote Keyswitch To install the ADEMCO 4146 keyswitch, perform the following steps: Step 1 2 Action Connect the ADEMCO 4146 to the panel as shown in Figure 3-20. If you are using the tamper, make sure it is connected to a zone. Use this output to trigger a low current relay, and wire the power for the smoke detectors through the relay’s contacts. Connect trigger input of the relay to Output 1 on J7. Connect the “pole” (common) of the relay to terminal 6 of the control. Connect the positive side of the smoke detectors to the normally closed contact of the relay. Connect the negative side of the smoke detectors to terminal 7 of the control. All messages programmed for transmission via the phone lines may also be sent via the Communicator. These messages are transmitted in Contact ID format regardless of the format programmed for the control in fields 45 and 47. We recommend that, if possible, you use Contact ID for the main dialer.

    If Contact ID is not used, certain types of reports are not sent. These options are accessed through data fields,56 and,57, respectively. The Dynamic Signaling feature is designed to reduce the number of redundant reports sent to the central station. The feature is described as follows: Dynamic Signaling Delay (Field,56) Select the time the panel should wait for acknowledgment from the first reporting destination before it attempts to send a report to the second destination. Delays can be selected from 0 to 225 seconds, in 15-second increments. Dynamic Signaling Priority (Field,57) Select the initial reporting destination for reports, Primary Dialer (0) or Communicator (1). The chart below provides an explanation of how the Dynamic Signaling feature functions. Report is sent to both the Primary Phone No.Report is sent to both the Primary Phone No.Also, within an enabled category, the specific event must be enabled for dialer reporting. If, for instance, zone 10 is enabled to report, but zone 11 is not, zone 10 will report via the Communicator, but Zone 11 will not. If events occur at the same time, they are transmitted in order of priority. There are two subscriber IDs programmed into the Communicator: primary and secondary. These correspond to the two subscriber ID’s programmed into the control for each partition. If a subscriber ID for a partition is not programmed (disabling reports to that central station), the events enabled for the corresponding subscriber ID in the Communicator will not be transmitted. The first event in the queue is transmitted to both the primary and the secondary Communicator central stations before transmitting the second event. Installing the ECP Communicator To install the ECP Communicator, perform the following steps: Step 1 2 Action Mount the Communicator according to the instructions that accompany the Communicator.


  • Commentaires

    Aucun commentaire pour le moment

    Suivre le flux RSS des commentaires


    Ajouter un commentaire

    Nom / Pseudo :

    E-mail (facultatif) :

    Site Web (facultatif) :

    Commentaire :