• ademco vista 50 installation manual

    ademco vista 50 installation manual

    Download Link: ➡ ademco vista 50 installation manual



    File Name: ademco vista 50 installation manual.pdf
    Size: 3124 KB
    Type: PDF, ePub, eBook
    Category: Book
    Uploaded: 14 May 2019, 22:23 PM
    Rating: 4.6/5 from 652 votes.


    Last checked: 9 Minutes ago!









    ⬆ LINK ⬆




















    In order to read or download ademco vista 50 installation manual ebook, you need to create a FREE account.

    eBook includes PDF, ePub and Kindle version



    ✔ Register a free 1 month Trial Account.
    ✔ Download as many books as you like (Personal use)
    ✔ Cancel the membership at any time if not satisfied.
    ✔ Join Over 80000 Happy Readers


    Book Descriptions:

    ademco vista 50 installation manual

    Supports the 4286 VIP Module, which allows access to the system from either a remote location or on the premises Can control 8 separate areas independently, each functioning as if it had its own separate control. Provides a Common Lobby partition, which can be programmed to arm automatically when the last partition is armed, and to disarm when the first partition is disarmed. Provides a Master partition (9), used for the purpose of viewing the status of all partitions at the same time. It is the only format capable of uniquely reporting all 86 zones, as well as openings and closings for all 75 users. Supports upload and download capability of program and user information. Can print the event log on a serial printer using the 4100SM. Can view the event log on an alpha keypad. Provides a keypad macro command (macro is a series of keypad commands of up to 16 keystrokes) using the D key by partition. Provides cross-zone capability, which helps prevent false alarms by preventing a zone from going into alarm unless its cross-zone is also faulted within a 5-minute period. Contains a built-in User’s Manual, which provides the end user with a brief explanation of the function of a key when the user presses any of the function keys on the keypad for 5 seconds. Provides trigger outputs, which may interface with Communicator equipment or other devices such as keyswitch LEDs, printer, or pager. At least one 2-line alpha keypad (6160) must be connected to the system for programming (if you are using keypad programming), and must remain connected to the system in order to allow the primary user to program additional user codes into the system at a later time. These areas are called partitions. A Partitioned system allows the user to disarm certain areas while leaving other areas armed, or to limit access to certain areas to specific individuals. Each system user can be assigned to operate any or all partitions, and can be given a different authority level in each.

    • ademco vista 50 installation manual, ademco vista 50p installation manual, ademco vista 50 user manual, honeywell vista 50 installation manual, honeywell vista 50 user manual, ademco vista 50 user guide, honeywell vista 50p user manual, ademco vista 50 manual instalador, ademco vista 50 installation manual pdf, ademco vista 50 installation manual free, ademco vista 50 installation manual instructions, ademco vista 50 installation manual 2017, ademco vista 50 installation manual 2016, ademco vista 50 installation manual software, ademco vista 50 installation manual downloads, ademco vista 50 installation manual online, ademco vista 50 installation manual, ademco vista 50p installation manual, ademco vista 50 user manual, honeywell vista 50 installation manual, honeywell vista 50 user manual, ademco vista 50 user guide, honeywell vista 50p user manual, ademco vista 50 manual instalador, ademco vista 50 installation manual, ademco vista 50p installation manual.

    Product availability, at the moment, is in flux. If you order today, depending on the product, there may be a significant delay in shipping it to you. We apologize for any delays, and assure you that products will be shipped as soon as we can get them. Before COVID, we had significant stock of nearly every popular product that we sell. But demand has outpaced our supplier's ability to meet it, and has exhausted the stock we had purchased to meet increased demand during the government-mandated lockdowns. If you need the product right away, it is unlikely we will be able to accommodate you. For that we apologize. We ask for your patience as we all navigate this unique situation together. Be nice to our employees, they are doing their best to answer your questions and get your product to you as quickly as they can.If you are here to get product quickly because you are unable to get the product at your usual supplier, rest assured, we are also out of the product and won't be able to fulfill your order in a timely manner. Like our end-users, we will be delivering products as soon as we get them in. For the purpose of improving our site, we’d like to know if you are one of the following: A-1 UL365 Police Station Connected Burglar Alarm. A-1 California State Fire Marshal (CSFM) and UL Residential Fire Battery Backup Requirements. A-2 Please read each warning carefully. This symbol also denotes warnings about physical harm to the user. These prompts are shown in a single-line box. Supports up to 16 2-wire smoke detectors on zone 1. Triggers the built-in sounders on other hardwired smoke detectors if one smoke detector annunciates an alarm. This feature requires a 4204 Relay Module. Supports up to 50 2-wire latching glassbreak detectors on zone 8. Supports up to 77 additional expansion zones using a built-in polling (multiplex) loop.

    Otherwise, if no keys are pressed for 2 minutes, the system automatically returns to the master partition The sounder on a Master keypad reflects the sound of the most critical condition on all of the partitions. The priority of the sounds, from most to least critical, is as follows: 1. 2. 3. Pulsing fire alarm sounds Steady burglar alarm sounds Trouble sounds (rapid beeping). In order to affect that partition, the user must use a code that has access to that partition. Also, in order for a user of any partition to log on to Partition 9 to view the status of all partitions, that user must have access to all partitions. Otherwise, access is denied.A Master keypad uses the same panics as Partition 1. Master keypad panics are sent to Partition 1, and will activate on Partition 1. Therefore, panics must be programmed for Partition 1. DO NOT ATTEMPT TO REMOVE THE KNOCKOUTS AFTER THE CIRCUIT BOARD HAS BEEN INSTALLED. 2 Using fasteners or anchors (not supplied), mount the control cabinet to a sturdy wall in a clean, dry area that is not readily accessible to the general public. The back of the cabinet has 4 holes for this purpose. To provide certificated burglary service for UL installations, refer to the special requirements and Figure 3-2 Cabinet Attack Resistance Considerations to follow. For UL Commercial Burglary installations that require ATTACK RESISTANCE, use the COM-UL Commercial Enclosure. Insert the key into the lock. Position the lock in the hole, making certain that the latch will make contact with the latch bracket when the door is closed. When correctly positioned, push the lock until it is held securely by its snap tabs.Mount the clip-on tamper switch (supplied) to the cabinet's right side wall as shown in the diagram below, and wire it to one of the hardwire zones. Use a bell with a tamper-protected housing such as the AB12M. The bell housing's tamper switch and inner tamper linings must also be wired to the hardwire zone.

    Before anything can be assigned to those partitions, you must first determine how many partitions (1-8) are required. Following are some facts you need to know about partitioning. It can also be assigned to Partition 9 if Master keypad operation is desired. (See “Master Keypad Setup and Operation” later in this section.) The zones assigned to a partition will be displayed on that partition's keypad(s). Assign users to partitions. Program partition-specific fields (see the Data Field Descriptions section). An example of this might be in a medical building where there are two doctors’ offices and a common entrance area (see example that follows explanation). The Common Lobby feature employs logic for automatic arming and disarming of the common lobby. Two programming fields determine the way the common lobby will react relative to the status of other partitions.NOTE: In the tables below, the notations in parentheses ( ) indicate the current status of the other partition when the user takes action. Arming a partition causes the system to automatically attempt to arm the lobby. The following chart sums up how the common lobby partition will operate. Therefore, you would want to program a partition to affect and arm the lobby if the users of that partition are expected to be the last to leave the building. Only the partitions the user has access to are displayed.This causes the lobby to arm last. The lobby must be armed separately, after arming all affecting partitions first. A Master keypad reflects the status of the entire system (Partitions 1-8) on its display at one time. This is useful because it eliminates the need for a building security officer to have to log on to various partitions from one partition's keypad to find out where an alarm has occurred. The Armed LED on a Master keypad is lit only if all partitions have been armed successfully.

    Please check your wiring. Connect the additional keypads as shown in Figure 3-5, using the keypad wire colors shown.Selectable for confirmation of arming ding. Selectable for no timeout or timeout of 2-30 minutes. UL1023 Household Burglary Installations For Household Burglary installations, the total current drawn from the alarm output must not exceed 1.7A. A battery must be installed, as the battery supplies current from the combined auxiliary power, polling loop, and alarm output in excess of 750mA. Up to two 719 sirens can be used wired in parallel. The zone displays on the keypads, reports to the event log, and transmits to the central station (if programmed) on Partition 1. The Contact ID event code is 321, Bell Trouble. Wiring the Alarm Output The wiring of the alarm output depends upon whether you are going to supervise the output or not. Use the appropriate procedure below for your application. Using a Siren Driver To install a siren driver, perform the following steps: Step 1 2 3 4 Action Mount the siren driver in the panel’s cabinet. Wire the siren driver to the control and to the speaker(s). (See the driver’s instructions.) Cut the blue jumper on the upper left-hand corner of the panel’s PC board. Program Zone 98 with no response type (00). If a device such as a siren driver with a high-resistance trigger input (drawing less than 5mA) is used in a UL Household Fire installation, the siren driver must independently supervise siren speaker wiring. Cut the blue jumper on the upper left-hand corner of the panel’s PC board. Program Zone 98 with no response type (00). It is the only format capable of uniquely reporting all 86 zones, as well as openings and closings for all 75 users. This requires central stations to be equipped with the MX8000 receiver or equivalent. If you need to update your MX8000 receiver, contact your distributor. To prevent the risk of shock, disconnect phone lines at the telco jack before servicing.

    Assign the tampers’ hardwire zone to a burglary partition. Program it for 24-hr.All wiring between the bell and panel must be run in conduit. Remaining wires do not need to be run in conduit. All wiring that is not run in conduit must exit from the knockout openings on the bottom or back of the cabinet. Mount a shock sensor such as Sentrol No. 5402 to the control's backbox. Follow the manufacturer's instructions for proper sensor mounting. This sensor also must be wired to a hardwire zone. For safe and vault applications, a UL Listed contact must be used inside the cabinet through one of the knockouts for pry-off tamper purposes. This sensor also must be wired to a hardwire zone. Refer to Figure 3-3 (Detail B). Make sure the clip orientation is exactly as shown in the diagram to avoid damage. This will also avoid problems with insertion and removal of the PC board. 2 3 Insert the top of the circuit board into the slots at the top of the cabinet. Make certain that the board rests in the slots as indicated (Detail A). Swing the base of the board into the mounting clips and secure the board to the cabinet with the accompanying screws. Make certain that the mounting screws are tight. This ensures that there is a good ground connection between the PC board and the cabinet. Dress field wiring away from the microprocessor (center) section of the PC board. Use the loops on the left and right sidewalls of the cabinet for anchoring field wiring using tie wraps (Detail C). These steps are important to minimize the risk of panel RF interference with television reception.The 2-line alpha display, 6160may be used. The maximum wire run length from the control to a keypad, which is homerun back to the control must not exceed the lengths listed in the table. Run field wiring from the control to the keypads (using standard 4-conductor cable of the wire gauge determined in step 1). Connect the keypad(s) to terminals 6, 7, 8, and 9 on the control board, as shown in Figure 3-4.

    Refer to the device’s instructions for the DIP Switch Tables. Mount each device in the desired location. Refer to the device’s instructions. Run wires from the control panel to each device on the polling loop (see Figure 3-13). No individual wire run may exceed the lengths shown in the following table.NOTE: If you are using serial number devices, and intend to enroll each device through the keypad automatically, wire no more than 25 of these devices to the control at a time. Then power up and program them before connecting the next 25. Leave previously enrolled devices connected. If you intend to manually enter the serial numbers through the keypad or through Compass downloading software, all the devices may be connected before powering up to program. If the panel is armed when a device fails, and the zone is a burglary zone, the will go into alarm Refer to Figures 3-14 and 3-15, to follow.Supervised transmitters send a supervisory signal every 70-90 minutes. Zones 88 and 90 are used to supervise the RF reception of receivers 2 and 1, respectively. Proper RF reception is impeded (i.e., jamming or other RF interference). The control checks for this condition every 45 seconds.Use two identical receivers to provide either a greater area of coverage or redundant protection. They must be set for different addresses. Any zone from 1 to 86 can be used as a 5800 Series wireless zone, with the exception of zone 64 (reserved for a wireless keypad). Do not place it on or near metal objects. Install the RF receiver at least 10 feet from the control panel or any keypads, to avoid interference from the microprocessors in these units. If dual receivers are used: a. b. c. d. They must be at least 10 feet from each other, as well as from the control panel and remote keypads. Each receiver must be set to a different device address. The receiver set to the lower address is considered the 1st RF receiver for supervisory purposes. The House IDs must be the same.

    Installation and Setup of the RF Receivers To install the RF receiver, perform the following steps: Step 1 2 3 4 Action Mount the receiver, following the advisories stated previously. Set the DIP switches in the receiver for the address (01-07). See Figure 3-16. Make sure the address setting is not being used by another device (keypad, relay module, etc.). Connect the receiver’s wire harness to the keypad terminals (6, 7, 8, and 9). Plug the connector at the other end of the harness into the receiver. Refer to the Installation Instructions provided with the receiver for installations regarding antenna mounting, etc. To install the 5800TM, perform the following steps: Step 1 Action Mount the unit using its accompanying mounting bracket near the RF receiver. The 5800TM must not be installed within the control cabinet. It must be between 1 and 2 feet from the receiver’s antennas. 2 Set the module for the appropriate address. For Address Setting 28 cut the red jumper; for Address 29 cut the white jumper; for Address 30 cut both jumpers. Make sure the address setting is not being used by another device (keypad, relay module, etc.). 3 Connect the module’s wire harness to the keypad terminals (6, 7, 8, and 9). Plug the connector at the other end of the harness into the module. The receiver now “sniffs” out any House IDs in the area and displays them. Keep the receiver in this mode for about 2 hours. Use a House ID that is not displayed. As Sniffer mode effectively disables RF point reception, Sniffer mode cannot be entered while any partition is armed. Transmitter Input Types All transmitters have one or more unique factory-assigned input (loop) codes. Transmitters can be programmed as one of the following types:The transmitter must remain within the receiver’s range. Sends all the signals that the RF type does, but the control does not supervise the check-in signals. The transmitter may therefore be carried off-premises. These send only fault signals.

    If the communicator is connected to a PABX, be sure it has a backup power supply that can support the PABX for 24 hours (central station) or 60 hours (remote station). Many PABXs are not power-backed up, and this can result in a communication failure if power is lost.The 2K EOL resistor must be connected in series with the devices, following the last device. Connect N.O. devices in parallel (across) the loop. The 2K EOL resistor must be connected across the loop wires at the last device.The alarm current on zone 1 supports only one smoke detector in the alarmed state. Compatible 2-Wire Smoke DetectorsTo wire 2-wire smoke detectors to zone 1, perform the following steps: Step 1 2 3 Action Select up to 16 2-wire smoke detectors from the list of compatible detectors. Connect 2-wire smoke detectors across zone 1 terminals (10 and 11) as shown in Figure 3-10. Observe proper polarity when connecting the detectors. Connect the EOL resistor at the last detector in the loop across the zone 1 terminals. The EOL resistor must be connected across the loop wires at the last detector. Auxiliary power to 4-wire smoke detectors is not automatically reset after an alarm, and therefore must be momentarily interrupted using a 4204 Relay Module. Compatible 4-Wire Smoke Detectors Use any UL Listed 4-wire smoke detector that is rated for 10-14VDC operation and that has alarm reset time not exceeding 6 seconds. Some compatible 4-wire smoke detectors are listed below.Connect detectors (including heat detectors, if used) across terminals of the zone selected. All detectors must be wired in parallel. See Figure 3-11. Connect the EOLR at the last detector in the loop across the zone’s terminals. You must connect the EOLR across the loop wires at the last detector. The zone provides enough standby current to power up to 50 2-wire glassbreak detectors meeting the requirements listed below.

    Compatible Glassbreak Detectors Use detectors that meet the following ratings:Connect detectors across zone 8 (terminals 21 and 22). See Figure 3-12. Connect the EOL resistor at the last detector in the loop across the zone’s terminals. You must connect the EOL resistor across the loop wires at the last detector. The maximum current draw of all devices on the polling loop cannot total more than 64mA (unless the system uses a 4297 Polling Loop Extender Module). Devices that can be programmed via either DIP switches or the built-in unique serial number must be set for the serial number mode operation. You can wire from device to device, or have multiple branches connected directly to the control panel in a star configuration. Compatible Polling Loop DevicesThe 4190SN right loop must not be used, and the left loop must be EOLR-supervised. The 4297 must be powered from the control panel’s Auxiliary Power Output or from a UL Listed supplementary power supply. In many cases, existing non-twisted pair wiring may be used, but it is more susceptible to interference from other sources, and may be problematic in installations with long wire runs or in high noise environments. Always locate polling loop wiring at least six inches (15cm) of AC power, telephone, or intercom wiring. The polling loop carries data between the control panel and the devices; interference on this loop can cause an interruption of communication. The polling loop can also cause outgoing interference on the intercom or phone lines. If this spacing cannot be achieved, shielded wire must be used. (Note that the maximum total wire length supported is cut in half when shielded wire is used.) When a star configuration is used, the total length of all wire runs combined cannot exceed 4000 ft (2000 ft.To install polling loop devices, perform the following steps: Step 1 2 3 4 Action Select devices from the list of compatible devices shown previously. Set the DIP switches in the device (if required).

    They do not send low-battery signals until they are activated. The transmitter may be carried off-premises. If at least one check-in is not received from each supervised transmitter within a programmed period (field 1?31), the “missing” transmitter number(s) and “CHECK” or “TRBL” are displayed. Unsupervised RF transmitters (5802MN, 5804) may be carried off the premises. Some transmitters have built-in tamper protection, and annunciate a “CHECK” or “TRBL” condition if covers are removed. If a loss of supervision occurs on a transmitter programmed for Fire, it reports in Contact ID as a Fire Trouble (373), not Loss of Supervision (381), to the central station. Transmitter Battery Life Batteries in the wireless transmitters may last from 4 to 7 years, depending on the environment, usage, and the specific wireless device being used. Factors such as humidity, high or low temperatures, as well as large swings in temperature may all reduce the actual battery life in a given installation. The wireless system can identify a true low battery situation, thus allowing the dealer or user of the system time to arrange a change of battery and maintain protection for that point within the system. Button-type transmitters (e.g., 5801, 5802, 5802CP and 5804) should be periodically tested, as these transmitters do not send supervisory check-in signals.Each device must be programmed as to how to act (ACTION), when to activate (START), and when to deactivate (STOP). Installing the 4204 Relay Modules Each 4204 module provides 4 relays with Form C (normally open and normally closed) contacts. To install the relay modules, see Figure 3-17 and perform the following steps: Step 1 2 3 Action Set the 4204’s DIP switches for a device address 01-15. Do not use an address being used by another device (keypads, RF receivers, etc.). Mount the 4204 Module per the instructions provided with them. Connect the module’s wire harness to the control (6, 7, 8, and 9).

    Plug the connector (other end of harness) to the module. If you are mounting remotely, homerun each module to the control. The table below shows the maximum wire run lengths.X-10 devices require the use of a 1361X10 transformer in place of the regular 1361 transformer. X-10 devices respond to “on” and “off” commands sent from the panel through the 1361X10 transformer. To connect the 1361X10 transformer, see Connecting the Transformer, later in this section. The keyswitch is wired across zone 7. This zone is no longer available as a protection zone. The keyswitch LEDs indicate the partition’s status (see table below). A momentary short across Zone 7 silences alarm bell and keypad sounds, and disarms the system if it was armed. A subsequent short across Zone 7 clears the alarm memory indication and resets 2-wire smoke and glassbreak detectors (if used). LED IndicationsFor UL Commercial Burglary installations, the tamper switch must be wired to a zone (zone 7 in Figure 3-18). When the keyswitch is removed from the wall, the tamper switch opens, causing an alarm or trouble on the zone. This also causes the control to disable keyswitch operation until the tamper is restored and the associated partition is disarmed. Wiring for the Remote Keyswitch To install the 4146 keyswitch, perform the following steps: Step 1 2 Action Connect the 4146 to the panel as shown in Figure 3-18. If you are using the tamper, make sure it is connected to a zone.One application of this feature might be to produce chime sounds at a distant location from the panel's keypads. Refer to the installation instructions that accompany your radio for the connections to the control panel. NOTE: See SECTION 4: Programming for the programming details when using the 4100SM. Connect terminal 6 on the 4100SM to the Brown wire on the 4142TR cable. Connect the 4142TR cable to J8 on the control. Connect terminals 8 and 7 of the 4100SM to terminals 6 and 7 (aux.

    Connect the UL EDP Listed serial printer to the 4100SM Interface Module. The 4100SM Module is supplied with a 10-foot RS232 cable.Power (-) 4100SM SERIAL MODULEThis may be done either from the premises or by calling the premises from a remote location. Only one VIP Module can be used in a security system.Allows the user to control relays using the telephone keypad. Provides voice annunciation over the phone to confirm any command that is entered. Announces many of the same words that would normally be displayed on an alpha keypad under the same system conditions. Can be supervised for connection to control panel (annunciated and reported as Zone 87). It listens for TouchTones on the phone line and reports them to the control panel. During on-premises phone access, it powers the premises phones.If you mount the VIP Module inside the control cabinet, attach it to the cabinet’s interior surface with 2-faced adhesive tape. You may leave the module’s cover off if it is mounted within the cabinet. If you mount the module outside the cabinet, use the screw holes at the rear to mount horizontally or vertically (2-faced adhesive tape may be used, if preferred). 2 3 4 Affix the 4286 connections label (supplied separately) to the inside of the VIP Module’s cover, if the cover is used. Otherwise, affix the label to the inside of the control cabinet’s door. These are the same connections as for remote keypads. Connect the module to the phone line as shown below. See Figure 3-21.Make connections exactly as shown in Figure 3-12. This is essential, even if the system is not connected to a central station.IF CONNECTING 2 SPEAKERS, USE 4-ohm or 8-ohm SPEAKERS AND CONNECT IN SERIES.Contact ID is the only reporting format that will send a “Listen-in to Follow.” If you are also using a 4286 VIP Module, be sure to follow Figure 3-22 when making connections.

    The UVCM board has a DC power jack and a 34-position terminal block for making connections to a DC power source, UVSTs, telephone lines, music source, or to the 4286 VIP Module; and to a control panel’s voice trigger and bell outputs (if required). Refer Figure 3-22 for wiring connections. For a detailed explanation of the wiring connections and the functions of the DC power jack and terminal block positions, refer to the installation instructions that accompany the UVS. If the phone plug is disconnected from the control, the premise’s phones will not operate. Sirens are restored if the alarm timeout period has not expired. As part of its fail-safe software, the control limits all audio alarm verification sessions to 15 minutes. This is because once the session begins, the AAV Module controls the duration. If a new Fire alarm should occur during a session, the control breaks the phone connection and sends the new Fire Alarm report, then re-triggers the AAV Mode. All other dialer messages triggered during ongoing conversation are held until either the AAV Module signals that it is inactive, or the 15-minute timeout occurs. If you are using X-10 devices, the 1361X10 transformer interface must be used instead of the regular 1361 transformer. The 1361X10 supplies the control panel with AC, and also sends control pulses through the premises electrical system to control the X-10 devices. The following table shows the maximum current that may be drawn from each output. Output Auxiliary Power Polling Loop Alarm Output Maximum Current Draw 750mA 64mA 1.7A. For Household Burglary-Only Installations: The total current drawn from the alarm output may be up to 1.7A. A battery must be installed to supply the current of the combined auxiliary power, polling loop, and alarm output in excess of 750mA. Failure to observe the polling loop current rating will cause polling loop malfunction.

    Failure to observe the auxiliary power current rating will result in a battery that does not charge properly or possibly a tripped circuit breaker. To connect the transformer to the control, perform the following steps: Step 1 2 3 Action Connect all installed devices to the control. Wire the 1361 Transformer (1361CN in Canada) to the panel (before connecting the battery) as shown in Figure 3-23, or wire the 1361X10 Transformer as shown in Figure 3-24 (if using X-10 devices). Plug the transformer into a 24-hour, uninterrupted, 120VAC, 60Hz outlet. After a few seconds, the keypad display appears.AC Power Outlet Ground: Available from 3-prong, 120VAC, power outlets only. To test the integrity of the ground terminal, use a 3-wire circuit tester with neon lamp indicators, such as the UL-Listed Ideal Model 61-035, or equivalent, available at most electrical supply stores. Calculate total current draw on the polling loop.If total load exceeds 64mA, then a 4297 Loop Extender Module can be used. Note that the total number of points connected to the panel cannot exceed 77. Calculate standby and alarm currents, then add to get Auxiliary Power current subtotal.Calculate alarm currents, then add to get the Alarm Output current subtotal.The COM-UL Commercial Enclosure can house batteries of up to 12V, 17.2AH and that may be used with this panel. The total standby current drawn from the auxiliary power and polling loop outputs combined must be limited to 270mA when 14AH batteries are used; and to 390mA when 17.2AH batteries are used. These batteries require a different charging voltage than is supplied by the panel. A dual battery harness is supplied that allows two batteries to be wired in parallel for increased capacity. 5. Using the total calculated from Table 4, calculate the battery capacity required for the installation. For 24-hour standby time: Total standby current X 24 hours X 1.1 contingency factor. Alarm Capacity For 4-, 5-, or 15-minute alarm time: Total alarm curr.


  • Commentaires

    Aucun commentaire pour le moment

    Suivre le flux RSS des commentaires


    Ajouter un commentaire

    Nom / Pseudo :

    E-mail (facultatif) :

    Site Web (facultatif) :

    Commentaire :